Test results checker

Type in a reading from your tester and see whether it meets BS 7671. Pick the test first.

  • V – Voltage
  • I – Current
  • R – Resistance
Test
MΩ

If your tester shows an over-range reading such as >299, type it as it appears.

Insulation resistance

–MΩ
Test voltage–
Minimum allowed–
–

Limits are from BS 7671:2018+A4:2026 and IET guidance. Check against your copy of BS 7671 or the On-Site Guide before relying on a result.

Checking an earth fault loop reading? Use the Max Zs calculator: pick the breaker and enter your measured Zs.

Insulation resistance

Test with the DC voltage for the circuit's band and compare the reading with the minimum (BS 7671 Table 64).

CircuitTest voltageMinimum
SELV and PELV250 V DC0.5 MΩ
Up to 500 V, including 230 V and 400 V500 V DC1 MΩ
Above 500 V1000 V DC1 MΩ

Since Amendment 2 (2022), where equipment that could be damaged by the test is left connected, a 250 V DC test between the live conductors and the protective conductor must read at least 1 MΩ. Some manufacturers still want their equipment disconnected first.

RCD trip time

Test at the RCD's rated residual current, 1 × IΔn (30 mA for a 30 mA RCD).

RCD typeTrip time at 1 × IΔn
General (non-delay)300 ms or less
Type S (time-delayed)Between 130 ms and 500 ms

BS 7671 has not required a 5 × IΔn test since Amendment 2, though it can still help with fault finding. Check the RCD type is right for the load too: Amendment 4 makes the Type AC, A and F requirements clearer.

Ring final continuity

  1. End to end. Measure line (r1), neutral (rn) and CPC (r2) from one end of the ring to the other. r1 and rn should be about equal: within 0.05 Ω is a common rule of thumb. For 2.5/1.5 mm² twin and earth, r2 should be about 1.67 × r1, because the CPC is smaller.
  2. Line to neutral. Cross-connect line and neutral of the two ends. Every socket should then read about (r1 + rn) ÷ 4.
  3. Line to CPC. Cross-connect line and CPC. Every socket should read about (r1 + r2) ÷ 4. This is R1 + R2 for the ring, which you record.

A socket that reads noticeably higher than the rest is likely to be on a spur, or to have a poor connection. The 1.67 ratio comes from the conductor sizes; the real resistance ratio is slightly lower, so the checker only flags a ratio more than about 10 % away.

Worked example

A 2.5/1.5 mm² ring reads r1 = 0.52 Ω, rn = 0.52 Ω and r2 = 0.86 Ω end to end. Line to neutral at each socket: (0.52 + 0.52) ÷ 4 = 0.26 Ω. R1 + R2 at each socket: (0.52 + 0.86) ÷ 4 = 0.345 Ω. The ratio 0.86 ÷ 0.52 = 1.65 is close to 1.67, so the CPC is continuous and the right size.