Voltage drop calculator

Check a cable run against the 3 % limit for lighting and 5 % for other circuits on a 230 V supply.

Circuit type
A
m

One-way length of the run, not there and back.

Voltage drop

–V
Of supply–
Limit–
Longest run allowed–

Values are for 70 °C thermoplastic flat twin and earth cable at full operating temperature. Check against your copy of BS 7671 or the On-Site Guide before relying on a result.

The formula

Vd = (mV/A/m × Ib × L) ÷ 1000

mV/A/m is the cable's voltage drop per amp per metre, from BS 7671 Appendix 4. Ib is the design current and L the one-way length in metres. The tabulated figure already allows for both the line and neutral conductors.

The limits

For an installation supplied from the public low-voltage network, BS 7671 (Regulation 525 and its voltage drop guidance) gives 3 % for lighting and 5 % for other uses. On 230 V that is 6.9 V and 11.5 V.

Worked example

A 2.5 mm² twin and earth radial carrying 20 A over 30 m: (18 × 20 × 30) ÷ 1000 = 10.8 V, which is 4.7 % and inside the 5 % limit.