Installation technology · Topic 2 of 5
Supply systems and earthing arrangements
The DNO delivers electricity to the building. How the installation gets its connection to earth depends on the type of supply.
- V – Voltage
- I – Current
- R – Resistance
- f – Frequency
The UK supply
- Single phase: 230 V between line and neutral.
- Three phase: 400 V between lines (230 V × √3 ≈ 400 V), and 230 V from any line to neutral.
- Frequency: 50 Hz.
- Under ESQCR, the voltage can vary from 10 % above to 6 % below 230 V.
Conductor colours
| Conductor | Colour |
|---|---|
| Line (single phase) | Brown |
| Lines L1, L2, L3 (three phase) | Brown, black, grey |
| Neutral | Blue |
| Protective conductor (earth) | Green and yellow |
Earthing arrangements
The letters tell you how the system is earthed:
- First letter T: the supply is connected directly to earth (Terre) at the transformer.
- Second letter N: the installation's earth is connected to the supply's neutral or earth conductor. T: the installation has its own earth electrode.
- S: separate neutral and earth conductors. C: combined neutral and earth.
| System | How the installation is earthed | Typical maximum Ze |
|---|---|---|
| TN-S | Separate earth, usually the lead sheath or armour of the supply cable | 0.8 Ω |
| TN-C-S (PME) | Combined neutral and earth (PEN) in the supply cable, split at the cut-out | 0.35 Ω |
| TT | The installation's own earth electrode (rod) | 21 Ω |
Ze is the external earth fault loop impedance: the part of the loop outside the installation. The figures above are the long-standing industry values for a 230 V single-phase supply up to 100 A. DNOs aren't obliged to meet them, so always measure Ze.
Exam tip: TN-C-S is the most common supply on new UK homes. TT is common in rural areas with overhead lines, and needs RCD protection because its Ze is high.