Supply systems and earthing arrangements

About 3 minutes · Diagrams, worked examples and a mini test

The DNO delivers electricity to the building. How the installation gets its connection to earth depends on the type of supply.

  • V – Voltage
  • I – Current
  • R – Resistance
  • f – Frequency

The UK supply

  • Single phase: 230 V between line and neutral.
  • Three phase: 400 V between lines (230 V × √3 ≈ 400 V), and 230 V from any line to neutral.
  • Frequency: 50 Hz.
  • Under ESQCR, the voltage can vary from 10 % above to 6 % below 230 V.

Conductor colours

ConductorColour
Line (single phase)Brown
Lines L1, L2, L3 (three phase)Brown, black, grey
NeutralBlue
Protective conductor (earth)Green and yellow

Earthing arrangements

Three earthing arrangements. TN-S: line, neutral and a separate earth conductor run from the supply to the installation. TN-C-S: line and a combined neutral and earth conductor (PEN) run to the installation, where they are separated. TT: line and neutral only, with the installation earthed by its own earth electrode. SupplyHomeSupplyHomeSupplyHome PEN TN-STN-C-S (PME)TT Earth via cable sheathEarth via the neutralEarth via own rod

The letters tell you how the system is earthed:

  • First letter T: the supply is connected directly to earth (Terre) at the transformer.
  • Second letter N: the installation's earth is connected to the supply's neutral or earth conductor. T: the installation has its own earth electrode.
  • S: separate neutral and earth conductors. C: combined neutral and earth.
SystemHow the installation is earthedTypical maximum Ze
TN-SSeparate earth, usually the lead sheath or armour of the supply cable0.8 Ω
TN-C-S (PME)Combined neutral and earth (PEN) in the supply cable, split at the cut-out0.35 Ω
TTThe installation's own earth electrode (rod)21 Ω

Ze is the external earth fault loop impedance: the part of the loop outside the installation. The figures above are the long-standing industry values for a 230 V single-phase supply up to 100 A. DNOs aren't obliged to meet them, so always measure Ze.

Exam tip: TN-C-S is the most common supply on new UK homes. TT is common in rural areas with overhead lines, and needs RCD protection because its Ze is high.