What size cable for an electric shower?

An 8.5 or 9.5 kW shower usually needs a 40 A circuit: 6 mm² twin and earth if clipped direct, 10 mm² or bigger if it runs through insulation. Showers get no diversity, and they need their own circuit with 30 mA RCD protection.

  • V – Voltage
  • I – Current
  • P – Power

Step 1: find the current

Shower power is normally quoted at 240 V, so divide by 240 to get the rated current. On a 230 V supply it draws a little less, but design for the rated figure.

ShowerCurrent at 240 VAbout at 230 VUsual breaker
8.5 kW35.4 A33.9 A40 A
9.5 kW39.6 A37.9 A40 A
10.5 kW43.8 A41.9 A45 A or 50 A (check the maker's instructions)

A shower runs at full power for as long as it's on, so no diversity is applied: the design current is the full rated current.

Step 2: choose the cable for a 40 A circuit

Run lengths use the 39.6 A rated current of a 9.5 kW shower:

How the cable is runSmallest twin and earth for 40 ALongest run (voltage drop)Longer run? Next size up
Clipped direct to a wall or joist6 mm² (rated 47 A)up to 39 m10 mm²: up to 66 m
Above a plasterboard ceiling, insulation up to 100 mm10 mm² (rated 45 A)up to 66 m16 mm²: up to 103 m
In an insulated stud wall, touching the inner face10 mm² (rated 47 A)up to 66 m16 mm²: up to 103 m
In an insulated stud wall, not touching the inner face16 mm² (rated 42.5 A)up to 103 m–

For a 10.5 kW shower on a 50 A breaker, the cable must be rated for 50 A. That's 10 mm² clipped direct, or 16 mm² above an insulated ceiling.

Other things to check

  • Its own circuit from the consumer unit, never a spur off another circuit.
  • 30 mA RCD protection: all circuits in a room with a bath or shower need it.
  • A double-pole isolating switch, usually a ceiling pull-cord or a switch outside the bathroom.
  • Adding or altering a circuit in a bathroom is notifiable under Part P in England.
  • Check the maximum Zs for the breaker in the Max Zs table.

Assumes 70 °C flat twin and earth (6242Y), 230 V, an MCB or RCBO, 30 °C ambient, the circuit not bunched with others, and no thermal insulation round a clipped cable. Voltage drop limit 5 % (11.5 V), BS 7671 Table 4D5 values. Grouping, heat or insulation can need a bigger cable: check with the cable size calculator. For study and estimating only; the installing electrician must design and certify the circuit.